Review Details: RESIDENTIAL SOLAR v.1

Permit Number - T22CM04217
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/15/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review T22CM04217 (6334 E CALLE BELLATRIX TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Revision B has a code violation. See sheets PV-5, PV-5.1 and PV-6. The 4 awg conductor between the Backup Interface and the Main Service panel, and the 4 awg conductor between the Backup Interface and the Backup Load Panel, are undersized for the OCPD, E3705.5. The OCPD rating shall not exceed the allowable ampacity of conductor. OCPD protection provided is 100A, conductor ampacity rating (after corrections) is 86.45A (see also calculations on sheet PV-6). Provide a minimum conductor sized of 3 awg for these two portions of the design.