Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.2
Permit Number - T22CM04192
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2023 | Site Engineering | NOT REQUIRED | |||
| 01/30/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/30/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: T22CM04192 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: DENIED 1. Include the proposed live and dead loads for the new open porch structure on the drawings. Information was not found on the resubmitted drawings. 2. Indicate that the new porch has been designed to withstand a minimum wind speed of 115 mph and seismic zone B or 2018 IRC R301.2(1). Note was not found on the resubmitted drawings. 3. Provide information on the drawings that indicate how the structure will comply with the required corner bracing on the drawings. Information was not found on the resubmitted drawings. 4. New Comment: Indicate the dimensions for the depth of the new glue lam beam, only the width is indicated. 5. New Comment: Indicate the size (2x4, 2x6, etc..) of the new “double king studs” on each end of the new glue lam beam in the corner bedroom. Indicate how the new point load will be supported at the foundation such as a widened footing or pier. 2018 R602.10.8. BUILDING REVIEW COMMENTS: DENIED 1. New comment: Provide a written response letter to the review comments that clarify the information and indicate what page the revisions can be found on the drawings. 2. New Comment: The drawings indicate that this is a permit submittal for a structure that has already been enclosed. Note on the drawings “the inspector may require work that has been covered to be exposed for inspection.“ 3. Provide a site plan to scale that reflects the actual measurements for the project. Verify that the proposed porch is to be only 1’-6” from the property line on Tennessee St. Provide a second dimension on the revised plan that shows the distance from the existing previously enclosed porch to the property line on Liberty St. The required setback shall be part of the Zoning review. 4. New comment: Verify the building evaluation cost for the project and include all work including the work that was previously done but is to be covered by this submittal such as the enclosing of the front porch. The scope of the project would appear to be greater than the $18,510.00 indicated. This should also include the new mechanical mini split systems to be installed. 5. Note on the plans that “All work will be done in accordance with the 2018 IRC and all adopted codes and ordinances of the City of Tucson”. This note was not found on the resubmitted drawings. 6. Provide location and size of the windows for both bedrooms that are being expanded and verify that they meet egress requirements per 2018 IRC 310. Egress windows shall indicate a minimum net clear opening of 5 sf with the maximum sill heigh of 44” above the finished floor. The clear opening shall be a minimum of 24” and 20” wide. The corner bedroom indicates (2) windows, but it is unclear if they are 2’ wide and 5’ in height? Clearly indicate the size and the window type (such as double hung) on the drawings. The center bedroom that is being expanded indicates a larger window but no height off of the floor or the window type. Indicate this information on the drawings as well. 7. New comment: Indicate the new square footage of the newly expanded bedrooms and the percentage of natural light and vent for each room. A minimum of 8% of the floor area of the room is required for natural lighting and a minimum of 4% of the floor area of the room is required for natural ventilation. R303.1. 8. Provide the energy information for the new windows that follow the 2018 IECC Table 402.1.2. Note that a maximum U factor of 0.40 is required with a minimum SHGC of 0.25. This information was not found on the resubmitted drawings. 9. Note the R value of the foam insulation on sheet 4 on the wall section for the ceiling. A minimum of R30 is required per the exception 2018 IECC for areas without attics. This note was not found on the resubmitted drawings on sheet 4. 10. New Comment: Note on the drawings that a permanent certificate shall be posted on a wall in the space where the furnace is located, a utility room or an approved location inside the building. The certificate shall indicate the energy performance of the new mechanical systems as well as the R-values of insulation installed in ceilings, roofs, walls, the duct insulation if installed outside of the conditioned space; U-factors and the solar heat gain coefficient (SHGC) of the windows. 2018 IECC R401.3. MECHANICAL REVIEW COMMENTS: DENIED 1. New Comment: The revised drawings indicate several new mini split mechanical units to be installed. Provide additional information on the units including the manufacture, size, type, heat pump and the electrical requirements (coordinate with the electrical plans). Show the location of the outdoor unit on the plans. 2. Note that ducts, air handlers and filter boxes shall be sealed. 2018 IRC M1601.4.1. Note was not found on the resubmitted drawings. ELECTRICAL REVIEW COMMENTS DENIED 1. Indicate all electrical including a light outside of the kitchen door and at least one GFCI outlet on the new open porch. Information note found on resubmitted drawings. Show the new open porch on the electrical plan and include all new electrical devices. 2. New Comment: Note on the drawings that all exterior lighting will be installed in accordance with the 2012 City of Tucson/Pima County Outdoor Lighting Code. 3. New comment: Indicate the location of the existing lighting for both bedrooms that are being expanded on the plans. At least one wall switched controlled lighting outlet shall be installed in every habitable room 2017 NEC 210.70(A)(1). 4. Note on the drawings that smoke detectors will be installed in the entire house, including the existing area. Indicate a smoke detector in the hallway outside of the bedroom doors. 2018 IRC R314.2. Note on the drawings that “all detectors shall be interconnected so that the actuation of one alarm will activate all.” 2018 IRC R314.4. 5. New Comment: Indicate the size of the electrical service (100 amp, 200 amp) and if it is existing, or if an upgrade will be required due to the additional loads. Indicate the location of the electrical service meter and the electrical panel on the drawing. Provide a panel schedule for the project. PLUMBING REVIEW COMMENTS: CONDITINALLY APPROVED No plumbing work is proposed as part of this submittal. If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
| 01/24/2023 | Site Zoning | REQUIRES RESUBMIT | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T22CM04192 Porch 4750 S LIBERTY AV Zoning C-2 TRANSMITTAL DATE: January 24, 2023 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. These comment are still applicable. 1.COMMENT: Provide a Residential Plot Plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. This shall in include: a. Lot coverage calculation that meets the requirements of UDC Article 6.4.3 & the example shown on the residential plot requirements. b. Zoning of adjacent parcels c. All Utility lines d. Property line distances In the link provided below is a Plot plan grid that can be used. https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Grid.pdf 2.COMMENT: Draw dimension and label the height of the new structure measured from design grade to top of wall. 3.COMMENT: Clarify why the structure is on two separate parcels. Please provide permit documentation. A lot combination may be required. 4.COMMENT: Additional comments may be forthcoming. Clarify any access easements If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
||
| 01/20/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |