Permit Number: T22CM04032
Parcel: 12108005A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM04032
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2022 Commercial Plumbing APPROVED
11/01/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/01/2022 Commercial Electrical REQUIRES RESUBMIT Per the Code Enforcement Inspectors report there are multiple electrical code violations both fire and non fire related on this site that are potential life threatening items and need to be addressed.
1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a Registered Design Professional. Provide complete electrical plans addressing the problems, and sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
11/01/2022 External Reviewers - Willdan REQUIRES RESUBMIT Activity Number: T22CM04032

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


DENIED:
Sheet 7 of 12; Coordinate with Registrant regarding observation and analysis of existing conditions and/or conditions resulting from exposure to fire and heat. Registrant to provide a full report. City permit process, review and inspections will follow once report is submitted based upon engineers recommendations.
Report Sheet 7 of 12, 2018 IBC 1603.1General.Construction documents shall show the size, section and relative locations of structural members with floor levels, column centers and offsets dimensioned. The design loads and other information pertinent to the structural design required by Sections 1603.1.1 through 1603.1.9 shall be indicated on the construction documents.
Report Sheet 7; 2018 IBC 1604.4; Analysis.Load effects on structural members and their connections shall be determined by methods of structural analysis that take into account equilibrium, general stability, geometric compatibility and both short- and longterm material properties. Submit calculations to demonstrate compliance with this requirement that coincide with structural details.
Sheet T-1; Plans do not include structural details based upon the Engineers recommendations. Submit sealed structural framing details.
Sheet T-1, 2018 IEBC 301.2 Repairs.Repairs shall comply with the requirements of Chapter 4. Based upon the Engineers Report identifying substantial structural damage and repairs (2018 IEBC [BS] 405.2.3), review the 2018 IEBC and demonstrate compliance with applicable sections


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov