Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - T22CM03994
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/15/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/15/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: T22CM03994 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved All corrections complied Approved/Subject to field approval ELECTRICAL REVIEW COMMENTS Conditionally Approved E6.1 Electrical Panel Schedules: Comment only, NH1 & 2 don’t need 1000 amp buses PLUMBING REVIEW COMMENTS: Denied Fourth Plumbing Review: 1 thru 4 OK 5). SAME- Now that plumbing plans have been included, they need to be accompanied by the civil plans for water service & sewer continuation as stated on plumbing pages. -IPC 106.3.1 **The development plan submitted with submittal #1 only has paving pages included** If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
03/13/2023 | PDSD Application Completeness | REVIEW COMPLETED |