Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.2
Permit Number - T22CM03991
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/09/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/07/2023 | Residential Building | REQUIRES RESUBMIT | T22CM03991 3rd PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. Place the (2018 IRC) code reference on the plans. Provide a .PDF file type. Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits FLOOR PLAN: Provide a (separate full sheet size) complete floor plan. SECTIONS - DETAILS: Show a complete cross-section detail of the proposed exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5. The framed wall may require a concrete stem for achieving the 6” clearance between framing and ground (R317.1 item 5). This detail is for the new wall at the enclosed vehicle door area. ELECTRICAL PLANS: Show a smoke alarm location near each side of the bedroom door, R314.3.2. Show receptacle outlets on all walls (within 6 feet of a door opening) and not more than 12 feet apart, E3901.2. Show all bedroom circuits including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.16. Provide a note for this circuit breaker requirement. INTERNATIONAL ENERGY CONSERVATION CODE: Provide insulation details minimum (R-13 walls and R-30 small additions or otherwise R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better. Show the type and value of wall and ceiling insulation. If you have any questions, please contact: Ken Van Karsen PDSD-Residential@tucsonaz.gov City of Tucson Residential Plan Review |
||
11/09/2023 | Site Zoning | REQUIRES RESUBMIT | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: PROJECT: T22CM03991 1755 E Calle Grandiosa Enclose garage (4th Review) TRANSMITTAL DATE:November 9, 2023 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Unfortunately the site plan provided is corrupted, zoning is unable to view these files, This comment are still applicable 1.COMMENT: Provide a Residential Plot Plan that meets the requirements found at: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements.pdf This shall in include: a. Lot coverage calculation that meets the requirements of UDC Article 6.4.3 & the example shown on the residential plot requirements. (Lot coverage must include vehicular use area whether improved or unimproved) . Lot coverage does not include porches, UDC Article 6.4.3.C.1.a but does include vehicle use area measured within the outside edges of any area allocated to vehicle use, whether improved or unimproved. b. Zoning of adjacent parcels c. All Utility lines d. Property line distances If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
||
10/26/2023 | PDSD Application Completeness | REVIEW COMPLETED |