Permit Number: T22CM03945
Parcel: 14036006A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - T22CM03945
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/09/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM03945
GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Sheet G003: This page still states that an automatic sprinkler system will not be provided. The comment response letter stated that this language would be corrected. It has not been corrected. Additionally, the deferred/separate submittal list does not include the sprinkler system. Also, the section provided on G-003 does not apply to this project as it only applies to S-2 occupancies. It appears that these corrections have not been corrected. Permit will not be issued until this page is corrected.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Third Plumbing Review:
1). OK
2).OK
3). OK
4). OK
5). SAME- water heater detail #11 on plan P-500 shows floor mounted installation, all other plumbing pages show elevated water heater. Plan pages need to correlate if elevated show support requirements & add pan to detail #11. -IPC 106.3.1 , 504.7 ** detail on P500 still shows floor mount water heater**(None of the 3 submitted plan sets sheet's page P500 show an elevated WH detail as shown in designer's response narrative. , all three show floor mounted detail, please add the detail to p500 that was displayed in the response narrative )


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/16/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
05/09/2023 Site Zoning REQUIRES RESUBMIT REVIEW TRANSMITTAL

FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM03945
Building Plans (3rd Review)
4711 E VALENCIA RD Zoning PAD-21

TRANSMITTAL: May 9, 2023

1. Zoning has reviewed the building plans for compliance with the associated unapproved Development Package DP22-0147. Zoning cannot approve the building plans until the DP is approved.


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
04/20/2023 PDSD Application Completeness REVIEW COMPLETED