Permit Number: T22CM03945
Parcel: 14036006A

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - T22CM03945
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2024 Water Sterilization Report (Deferred Submittal) APPROVED
12/18/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
12/18/2024 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT The heat pump split system,FC-2, has only 29% of the required outside airflow. Correct the deficiency and resubmit the report. Reference: Sections 403.3.1.2 and 403.3.1.5, IMC 2018.
12/18/2024 Concrete Installation Inspection (Deferred Submittal) REVIEW COMPLETED
12/18/2024 Masonry Inspection (Deferred Submittal) REVIEW COMPLETED
12/18/2024 Other Inspection Reports (Deferred Submittal) REVIEW COMPLETED BOLTS IN CONCRETE
12/18/2024 Other Inspection Reports (Deferred Submittal) REVIEW COMPLETED HIGH STRENGTH BOLTING
12/18/2024 Other Inspection Reports (Deferred Submittal) REVIEW COMPLETED REINFORCING STEEL
12/18/2024 PDSD Application Completeness REVIEW COMPLETED
12/18/2024 Post-Installed Anchor Inspection (Deferred Submittal) REVIEW COMPLETED
12/18/2024 Site Prep Inspection (Deferred Submittal) REVIEW COMPLETED