Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESTAMP - COMMERCIAL v.1
Permit Number - T22CM03879
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/17/2023 | Commercial Mechanical | APPROVED | |||
04/17/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
04/11/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comment and provide a written response. 1 Show lighting controls and verify compliance with the 2018 IECC for the revised lighting. Section C405 2918 IECC. 2 The electrical floor plan shows Panel ‘G1’ as New and the line diagram shows it as existing. Please clarify. 3 The KEYED NOTES on plan sheet E-2 is missing note #2. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC. |
||
04/12/2023 | Commercial Structural | REVIEW COMPLETED | |||
04/11/2023 | Fire New Construction | REVIEW COMPLETED |