Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM03862
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/25/2022 | Commercial Electrical | APPROVED | |||
| 01/04/2023 | Commercial Mechanical | APPROVED | |||
| 01/04/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/04/2023 | Commercial Plumbing | REQUIRES RESUBMIT | Southwest Gas, the local gas utility, provides natural gas at 7” WG, 2 PSIG, and 5 PSIG. Unless you have 2 PSIG gas service and a regulator located after the meter set to deliver gas at 8” WG or greater, Table 402.4(3), IFGC 2018 cannot be used. Also, even using Table 402.4(3), IFGC 2018, the gas pipe serving the kitchen appliances is undersized. Revise the design of the gas piping using the appropriate Table. Include the total developed pipe length from the gas meter to the furthest rooftop HVAC unit. Reference: Sections 402.1 and 402.3, IFGC 2018. [Second comment: There is insufficient information to review the modifications to the existing natural gas distribution system. Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the sizes, loads and developed lengths of the piping for the entire system. Reference: Section 107.2.1, IBC 2018.] [Initial comment: Provide plumbing plans for the demolition and the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2018.] | ||
| 11/25/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |