Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - T22CM03793
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/15/2022 | Site Engineering | APPROVED | |||
| 01/04/2023 | Site Zoning | APPROVED | |||
| 01/04/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/21/2022 | Commercial Electrical | REQUIRES RESUBMIT | The electrical re-submittal is not complete as requested per the previous electrical plan review comment. As well as the panel schedules and electrical notes; Please provide an electrical site plan showing the location of each gate on the premises, disconnecting means, wiring methods (conduit, conductors sizes) branch circuit and breaker panel designation, location of the breaker panels, electrical specifications for the gate operators/motors. Voltage drop calculations if applicable. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
| 12/28/2022 | Fire New Construction | REVIEW COMPLETED | |||
| 12/15/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |