Permit Number: T22CM03793
Parcel: 13321293B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM03793
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2022 Site Engineering APPROVED
01/04/2023 Site Zoning APPROVED
01/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/21/2022 Commercial Electrical REQUIRES RESUBMIT The electrical re-submittal is not complete as requested per the previous electrical plan review comment. As well as the panel schedules and electrical notes;

Please provide an electrical site plan showing the location of each gate on the premises, disconnecting means, wiring methods (conduit, conductors sizes) branch circuit and breaker panel designation, location of the breaker panels, electrical specifications for the gate operators/motors.

Voltage drop calculations if applicable.

Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
12/28/2022 Fire New Construction REVIEW COMPLETED
12/15/2022 PDSD Application Completeness Express REVIEW COMPLETED