Permit Number: T22CM03766
Parcel: 141019260

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - T22CM03766
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
12/08/2022 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT Exhaust fan EF-1-4 is operating approximately 33% below the design air flow rate and does not provide the minimum required exhaust flow rate for the two first floor restrooms. Contact the mechanical engineer of record for possible corrections to this deficiency and resubmit the balance report.