Permit Number: T22CM03715
Parcel: 132166160

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM03715
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/27/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM03715

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Approved
Reason:
Date Completed : 5/31/2022 2:46:58 PM


Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/25/2023 7:20:30 AM
1. Sheet A-1 structural plan shows new walkable ceiling structure but does not provide section showing the walkable height and method to access the mechanical units. Show at what height are the wall mounted mechanical unit with factory bracket in section.
2. Sheet A-1 does not show method and space of mechanical appliance access. 2018 IBC 306 requires “access to appliances or HVAC system components that utilize energy shall be accessible for inspection, service, repair and replacement without disabling the function of a fire-resistance-rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliances being inspection, serviced, repaired or replaced. A level working space not less than 30 inch deep and 30 inches wide shall be provided in front of the control side to service an appliance.”
3. Electrical sheets show double doors at grow room but A-1 and M-1 indicate single door. Coordinate drawings. Closed and open corridor do not match either.


Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/25/2023 9:39:00 PM
This mechanical review was approved on 5/18/2023 no cause for action


Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/27/2023 4:31:54 PM
Electrical Review
By: Ron Ross PE
Approved with comment below
E6.1: Panel A1 circuit breaker 2 is undersized for continuous lighting load. Upsize CB or reduce load for IFC set.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 10/9/2022 9:01:57 PM
Fourth Plumbing Review: OK Subject to field Inspections
1). OK- Donor sink water piping still not protected, needs to connect before backflow preventers same as the restrooms & drinking fountain are currently shown - OR if this sink is part the grow process add signage above - IPC 608.9.1 - OK Subject to Field Inspections
2 thru 4 OK
5). OK
6). OK
7). OK
8). OK - Field verify Planter table drain P-traps
9). OK - Self Contained eye wash station
10) OK
06/22/2023 PDSD Application Completeness REVIEW COMPLETED