Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM03715
Parcel: 132166160

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - T22CM03715
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/16/2024 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT The air balance report shows that exhaust fans, EF-1 and EF-2, have been deleted from the activity and that together, fresh air fans, FAF-1 and FAF-2, are able to achieve only 64% of the design airflow rate. The engineer of record shall review the situation, determine the course of action needed to ensure that the occupied areas have adequate ventilation, and submit a report showing how the proposed actions will resolve the ventilation shortfall prior to the air balance report being resubmitted. Reference: Section 403.3.1.5, IMC 2018.
02/12/2024 PDSD Application Completeness REVIEW COMPLETED