Permit Number: T22CM03546
Parcel: 10304001X

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - T22CM03546
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2023 Site Engineering APPROVED
05/31/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/26/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM03546

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 4/10/2023 8:05:43 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


Building(B) Reviewer (from previous submittal TUC7362001.052322)
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/26/2022 2:05:32 PM


Mechanical(M) Reviewer (from previous submittal TUC7362001.052322)
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 5/23/2022 10:57:45 PM
Approved/Subject to field approval


Electrical(E) Reviewer (from previous submittal TUC7362001.052322)
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/3/2022 5:55:48 PM
Electrical Review of Parks & Recreation
By: Ron Ross PE
E-4.1 ONE LINE DIAGRAM - WEST SERVICE: Keynote 5 calls out for a 400 amp panel vs MCB and dedicated note ‘SLW’ calls out for this panel as 600 amps. Correct/coordinate panel schedule with One Line.
ES-1.3 PARTIAL ELECTRICAL SITE PLAN: No keynote #11 provided.
ESD-1.1 PARTIAL ELECTRICAL SITE DEMOLITION PLAN: Missing Keynote #3.


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 5/26/2023 1:27:14 PM
Third Plumbing Review:
1). SAME-Lavatories need to be in the same room as the toilets- IPC 405.3.2, Update all affected pages**Response narrative states Building official approval has been granted, please upload those documents with the plan submittal. Document will need to include what was approved & by whom.**
2). SAME -There need to be the same number of lavatories as there are toilets. -IPC 403.1.3, Update all affected pages.
**Response narrative states Building official approval has been granted, please upload those documents with the plan submittal. Document will need to include what was approved & by whom.**
3). SAME-The required Sanitary connected Drinking Fountain on plan page L-1.10 can't receive storm water -IPC 1101.3 **
Since in close proximity restrooms on plan page L-1.5 suggest awning above drinking fountain or Or Provide Approval letter from Utility authority allowing the sewer connected water fountain to capture storm water**
4). OK
05/30/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: T22CM03546 Columbus Park (2nd Review)
3495 W EL CAMINO DEL CERRO Zoning RX-1

TRANSMITTAL DATE: May 30, 2023

1. COMMENT: Zoning has reviewed the building plan for compliance with DP22-0127 and although it appears that the building plans match the DP. The DP will need to be issued prior to this permit being issued.

2. The DP sheets provided in the building plans either need to be the stamped approved DP sheets, marked for reference only or removed from the building plan set.


If you have any questions about this transmittal, please contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov.
05/15/2023 PDSD Application Completeness REVIEW COMPLETED