Permit Number: T22CM03419
Parcel: 125100650

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM03419
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2022 Site Engineering APPROVED
11/01/2022 Site Zoning APPROVED
01/06/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/06/2023 Commercial Building REQUIRES RESUBMIT Previous review comments not addressed. See below.

1. General: As a Commercial project, all sheets in this submittal must be sealed, signed, and dated by a registered design professional per the IBC Section 107. Please provide.
2. General: Please provide structural calculations that verify the existing roof is capable of supporting the new loads from the PV system. These calculations must be sealed, signed, and dated by a registered design professional.
3. General: Please provide written responses to all review comments.
11/10/2022 Commercial Electrical REQUIRES RESUBMIT The previous 2 electrical review comments dated 6-27-2022 and 8-31-2022 are still not addressed for this current review. There was no electrical review response letter included. This is the comment, "Please address the electrical plan review comments and provide a written response"

"1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements"
11/08/2022 Fire New Construction REVIEW COMPLETED
11/01/2022 PDSD Application Completeness Express REVIEW COMPLETED