Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM03386
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/15/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/15/2022 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: T22CM03386 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: DENIED Following two review comments had remained un-resolved in the last cycle of review/ submission. Seems like in this cycle of response, the applicant over-looked the un-resolved structural items as they do not seem to have provided the answers and their response letter also states in error that structural items were resolved. REVIEW OPEN. 3. The design wind speed to be considered for wind uplift is 110 mph, this information is missing from the design documents. - response not acceptable as a reference to ASCE 7 design wind speed of 103 mph is made in the response whereas the City of Tucson amendments to the 2018 IBC code requires the design wind speed to be 110 mph minimum. So, the project needs to be re-evaluated to higher design wind speeds of 110 mph versus 105 mph it was designed to. Item OPEN. 4. Design for connectors is not provided, please use a minimum of 110 mph design wind speed when designing connectors for wind uplift. - item open, see 3 above. BUILDING REVIEW COMMENTS: APPROVED MECHANICAL REVIEW COMMENTS: CONDITIONALLY APPROVED All corrections complied Approved/Subject to field approval ELECTRICAL REVIEW COMMENTS9 APPROVED E2.1 Lighting Plan First Floor: Missing Keynote #7 PLUMBING REVIEW COMMENTS: CONDITIONALLY APPROVED Third Plumbing Review: OK Subject to Field Inspections 1). OK 2). OK 3). OK 4). OK 5). OK -water heater exhaust/intake updated on M2.0 6). OK 7).OK- Water dispenser Being added in lieu of High/Low drinking fountain -OK Subject to Field Inspections 8). OK 9). OK 10). OK If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
| 12/12/2022 | Fire New Construction | REQUIRES RESUBMIT | The building or structures constructed shall be within 400' of a fire hydrant and or additional hydrants shall be installed or fire sprinklers throughout the complete building. Hydrants in place exceed 400'. Hydrant shown is under brush and we will not jump over the fence and or drive through the fence and maneuver all the new landscape. As the hose lays is along the road to the property. Either install a hydrant at the entrance and or install fire sprinklers. Questions: Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
| 11/29/2022 | Site Engineering | REQUIRES RESUBMIT | 1. See Zoning Comment 2. Project: T22CM03386 Address: 8300 E Tanque Verde Rd This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.) Please start a new FUP at our permit application web page: https://tdc-online.tucsonaz.gov/#/home NOTE: Documentation of a cost estimate from your contractor will be required if this project involves any reconstruction, repair, rehabilitation, structurally connected addition, or other improvement of an existing structure (including TI’s and solar). Construction of separate builds/new structures does not require a cost estimate to be provided. Instructions: 1. Navigate into the current project in the “My Work” tab. Within the permit, navigate to the “Sub-Records” tab and click “Apply” on the Floodplain Use Permit Sub-Record 2. Locations -> Confirm the location is accurate to the project. Click “Next” 3. Type -> Fill in the “Square Feet” and “Valuation” boxes with the project area and a contractor-provided cost estimate (See note above: for new structures, input 0). Click “Next” 4. Contacts -> Confirm contacts and add any additional contacts if applicable. Click “Next” 5. More Info -> This will be filled in by the engineer assigned to your case, Click “Next” 6. Attachments -> Please attach the project plan, supporting documentation for the cost estimate (if applicable), and a drainage/hydrology report (if applicable). Click “Next” 7. Signature -> Read the statement and type your name. Sign your name below (You may Enable Type Signature to have the software sign for you.) Click “Next” 8. Review and Submit -> Review all information to ensure accuracy. Click “Submit” Contact Scott Haseman at scott.haseman@tucsonaz.gov, Stephen Blood at Stephen.Blood@tucsonaz.gov, or Loren Makus at Loren.Makus@tucsonaz.gov if you have any questions about the FUP. |
||
| 11/14/2022 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL PDSD Zoning Review PROJECT: T22CM03386 - DP22-0117 8300 E Tanque Verde Rd Animal Services - Expansion (3rd Review) TRANSMITTAL: November 14, 2022 This site is located in the SR zone (UDC 4.7.4). Animal Services is a permitted use in this zone (Table 4.8-1) subject to Use Specific Standard 4.9.4.D.5. Zoning has reviewed the building plans for compliance with DP22-0117 and although it appears that the plans match the DP, the DP must be approved by all review agencies before this building permit can be approved. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 11/08/2022 | Commercial Plumbing | REVIEW COMPLETED | for water | ||
| 11/08/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |