Permit Number: T22CM03004
Parcel: 138180510

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - T22CM03004
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2023 Site Engineering APPROVED
02/01/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/18/2023 Site Zoning REQUIRES RESUBMIT PROJECT: T22CM03004
6621 S Missiondale Rd - R-2
Convert Existing Garage to ADU (3rd Review)

TRANSMITTAL DATE:‎ January 18, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

The following comments shall be addressed prior to submitting for the required Design Development Option (DDO).

1. Based on aerial photos there is a porch along the east side of the existing dwelling that was built around 2020. Zoning was not able to find approved permit documents for the porch. You will need to either provide approved permit documents for this porch of secure permits for this porch. As this porch is attached to the main dwelling it cannot be part of this permit for the ADU. Zoning will not approve this permit until this comment is addressed.

2. The zoning provided on the site plan is not correct and should be R-2.


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on the wall height of 8’-4” provided for the south wall the required perimeter yard setback from the proposed ADU to the south property line is 6’-0”, proposed setback is 3’-8”.

A Design Development Option (DDO) must be submitted and approved to reduce the required setback,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. If you have questions about the DDO application or process, please contact Mark Castro at Mark.Castro@tucsonaz.gov.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
01/19/2023 Zoning Modifications - DDO REQUIRES RESUBMIT This site is located in the R-2 zone (UDC 4.7.9). An ADU is a permitted use in the R-2 zone, subject to use-specific standards 4.9.7.B.6, .9, & .10, and 6.6.3.

Per UDC Table 6.3-2.A, when a residential use is adjacent to a residential zone, the required interior setbacks are six feet or 2/3 the height of the proposed wall, whichever is greater, measured from the property line. Based on a wall height less than 9'-0", the required setback to the south property line is 6'-0"; proposed appears to be 3'-0".

A Design Development Option (DDO) is required to reduce this setback. The DDO application and requirements can be found here: https://www.tucsonaz.gov/files/pdsd/forms/2019_DDO_for_Setback_and_Height_UDC.pdf. The completed application shall be submitted as "Additional/Supporting Documentation" under activity number T22CM03004. Contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951 should you have questions about the DDO process.
01/04/2023 PDSD Application Completeness Express REVIEW COMPLETED
02/01/2023 Residential Building REVIEW COMPLETED T22CM03004 R2
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

A living space with cooking features (An ADU) is an independently functioning dwelling and requires compliance with the 2018 IRC, a Pima County issued address and collection of Impact Fee.

SITE PLAN:

1. Show the electric and water lines from property line to building, R106.1.1. Show all utility point of connections without dependance on another dwelling.
2. Show a street address for each dwelling on the site plan, R319.

PLANS:

1. Notate a cool (white) roof finish as required by the ADU provisions.

SECTIONS - DETAILS:

1. Clarify sheet A2 with legible details and notation.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe bypassing the existing dwelling and the water meter size.
2. Show an individual accessible water supply shut off for each dwelling unit, P2903.9.1

ELECTRICAL PLANS:

1. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Show an underground feeder from the primary service panel and continue to the more distant dwelling.
2. Update the Riser Diagram for the close dwelling and the feeder size to the detached dwelling panel, NEC 225.30 and E3403.
3. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
4. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.
5. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.
6. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity.

Please contact the plans reviewer if you have any questions: