Permit Number: T22CM03004
Parcel: 138180510

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.5

Permit Number - T22CM03004
Review Name: RESIDENTIAL NEW DWELLING v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2023 Site Zoning APPROVED
06/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/22/2023 Residential Building REQUIRES RESUBMIT T22CM03004 Repeat of comments provided 2/1/2023
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

A living space with cooking features (An ADU) is an independently functioning dwelling and requires compliance with the 2018 IRC, a Pima County issued address and collection of Impact Fee.

SITE PLAN:

1. Show the electric and water lines from property line to building, R106.1.1. Show all utility point of connections without dependance on another dwelling.
2. Show a street address for each dwelling on the site plan, R319.

PLANS:

1. Notate a cool (white) roof finish as required by the ADU provisions.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe bypassing the existing dwelling and the water meter size.
2. Show an individual accessible water supply shut off for each dwelling unit, P2903.9.1

ELECTRICAL PLANS:

1. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Show an underground feeder from the primary service panel and continue to the more distant dwelling.
2. Update the Riser Diagram for the close dwelling and the feeder size to the detached dwelling panel, NEC 225.30 and E3403.
3. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
4. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.
5. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.
6. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review