Permit Number: T22CM02925
Parcel: 125075880

Address:
301 N OLSEN AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T22CM02925
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2023 Zoning Modifications - DDO APPROVED
05/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/13/2023 Residential Building REQUIRES RESUBMIT T22CM02925
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes.

SITE PLAN:

1. Indicate the location and size of buildings, utility meters and lines supporting the alterations, R106.1.1. Show the utility lines requiring upgrade or replacement.

FLOOR PLANS:

1 Identify the room with a door entering into the dwelling. An opening from a garage directly into a sleeping room is not permitted, R302.5.1.

STRUCTURAL PLANS:

1. Show the garage floor direction of slope, R309.1. This requires a design with level concrete stems around the perimeter of a sloping floor.
2. Show a ½” gypsum board (garage side) on all walls common to the garage and house or other fire rated product in compliance with R302.6.
3. Garages beneath rooms require separation by not less than 5/8” type X gypsum board or equivalent. Also, ½” GWB is required on supporting walls, Table R302.6.

SECTIONS - DETAILS:

1 Show a cross-section detail of the proposed exterior wall, R106.1.1. Show 3/8” structural or ½” non-structural wall sheathing of the proposed exterior wall, R106.1.1.
2 Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.
3 Identify all fasteners for wind loading compliance. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.

ELECTRICAL PLANS:

1. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage and detached garages with service, E3703.5.
2. Garage Receptacle Location: an outlet is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review
03/14/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM02925
301 N Olsen Ave - R-1
Attached Garage & Play Room (3rd Review)

TRANSMITTAL: March 14, 2023

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a).
1. Based on a wall height of 14’-3” the required front street perimeter yard setback is 21’-5”, proposed setback is 19’-0”. The DDO must be approved prior to Zoning approval.

A Design Development Option (DDO) must be submitted and approved to reduce the required setback,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/17/2023 PDSD Application Completeness Express REVIEW COMPLETED
02/17/2023 Site Engineering REVIEW COMPLETED
02/17/2023 Site Landscape REVIEW COMPLETED