Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2023 Site Engineering NOT REQUIRED
04/25/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/18/2023 Residential Building REQUIRES RESUBMIT Permit Review T22CM02200 (7345 E 31ST ST TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken.

All code references are to the 2018 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

ELEVATION VIEWS:
1. Provide complete elevation views from foundation to roof assembly for each directional view of the carport and front porch, R106.1.1. The provided drawings show the rafter direction for the front porch changing by 90 degrees. Show the slope and height of the front porch after modification.

SECTIONS - DETAILS:
2. Provide consistent material and size references on details and notation, R106.1.1.
3. Provide a complete cross-section detail from foundation to roof assembly for modified front porch. Also show ledger board and connection to existing structural wall, R106.1.1. See https://www.tucsonaz.gov/files/pdsd/pdfs/Porch_Sample.pdf for examples.
4. Provide a cross-section detail of the rafter connections to the Ridge beam and rafter hangers being used, R106.1.1. (Ridge beam is listed as two 2x8s on the plans and spans from the corner of the house over the carport to the SW post.)
5. Provide a cross-section detail of the Ridge beam connection to the existing structural wall of the house.

STRUCTURAL PLANS:
6. Provide a structural glulam and engineered spec sheet for covering approximately 23.6’ span, R106.1.2, or provide a plan designed and sealed by a registered Arizona Engineer, R106.1. Ridge beam on plans is listed as two 2x8s is undersized for approximately 23.6’ span. Note Deadload of 10 psf, and Live load of 20 psf.
7. Provide updated plans showing Species, Grade, Size and spacing of rafters sufficient to span the given distance, R802.4.1. 2x8 rafters that will now span approximately 20’ are undersized.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
04/25/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM02200
7345 E 31ST ST Zoning R-1

TRANSMITTAL DATE:‎April 25, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: An elevation drawing will be required, so that zoning can verify the setback requirements



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov