Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - T22CM02001
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2022 | Commercial Electrical | APPROVED | |||
| 05/31/2022 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Comment not resolved. Provide specifications for the new HVAC system on the drawings. [Initial comment: The dwelling unit previously had an evaporative cooler, not an air conditioner. Provide specifications for the proposed HVAC unit and a heating/cooling load calculation to verify the required unit capacity.] 2. Comment not resolved. The note on the floor plan, A1/A1.1, still shows values for a minimum U-factor and a minimum SHGC. They should be maximum values. [Initial comment: Revise the window specifications to require a maximum U-factor of 0.40 and a maximum SHGC of 0.25.] |
||