Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM01860
Parcel: 132131260

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - T22CM01860
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2023 Water Sterilization Report (Deferred Submittal) APPROVED
09/14/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
09/14/2023 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT 1. The submitted air balance report is incomplete. The air balance report only addresses the eight rooftop units and does not provide any balancing information for the two make-up air units or the six exhaust systems. Hood capture and containment testing was not done.
2. The submitted air balance report is incorrect. The same system description and summary balancing results are used for each of the eight rooftop units. The unit descriptions, model numbers, and balancing criteria do not match the approved design drawings.
3. Energy Masters & Development Co. is not certified by either the Associated Air Balance Council (AABC) or the National Environmental Balancing Bureau (NEBB) and has not been previously approved as a balancing contractor by the City of Tucson. Reference: Section 403.3.1.5, IMC 2018, as amended by the City of Tucson.
09/13/2023 PDSD Application Completeness REVIEW COMPLETED