Permit Number: T22CM01601
Parcel: 11717044B

Address:
343 S SCOTT AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM01601
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2022 Commercial Plumbing APPROVED
10/28/2022 Site Engineering APPROVED
11/29/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/04/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM01601

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
Due to the change of occupancy submitted corrections dated on 6/17/2022 are cancelled see new corrections below
1. Provide fire dampers where ducts penetrate the 1 hour fire rated horizontal assembly between floors (IMC2018,607.6.1)
2. Provide ventilation calculations (IMC2018,403.3.1.1.1)
3. Kitchen exhaust duct shall be protected in an approved when penetrating the horizontal fire rated assembly in an approved manner, a chase is not acceptable and there is no fire damper allowed in kitchen exhaust ducts penetrations (IMC2018,505.505.5)
4. Provide firestop system for dryer and bathroom duct penetration's equal to astm e 119 or ul 263 (IMC2018,607.6.1)
5. Provide ceiling radiation dampers for bathroom exhaust fans mounted in ceiling (IMC2018,607.6.1)


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E7.0 Feeder Diagram: Need to upsize AL conductors for PNL E.


PLUMBING REVIEW COMMENTS:
Denied
Third PLUMBING REVIEW:
1 THRU 3 OK
4). SAME-Add the manufacturer name & model number info of the gas appliance that is to be installed in unit 4's fireplace to plan page P2.1 or P4.2 to show that it complies with -IFGC 303.3 #1 &#2, 304.5, & 602 ** NOT SHOWN ON ANY OTHER
PAGES AS STATED ON RESPONSE SHEET**
5 THRU 13 OK
14). OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/29/2022 Historic REQUIRES RESUBMIT Please submit the required documents noted in the Special Districts application via TDC Online. Information on the proposed AC units and new skylights should also be included in the plan set.
11/01/2022 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM01601
TI Multi Family
343 S Scott Ave Zoning HC-3


TRANSMITTAL DATE:‎November 1, 2022


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Zoning has reviewed the building plan for compliance with DP22-0225, Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
11/16/2022 Fire New Construction REVIEW COMPLETED