Permit Number: T22CM00946
Parcel: 13017149A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM00946
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2023 Commercial Mechanical APPROVED
06/15/2023 Commercial Structural APPROVED
05/25/2023 Site Engineering APPROVED
06/13/2023 Water - PDSD APPROVED
06/12/2023 Commercial Electrical NOT REQUIRED
06/15/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/13/2023 Commercial Plumbing REQUIRES RESUBMIT Provide a downstream vent for the grease interceptor. The vent pipe needs to rise vertically at least 6” above the flood rim of the grease interceptor before running horizontal. Reference: Section 905.5, IPC 2018.
05/13/2023 Fire New Construction REVIEW COMPLETED
05/12/2023 PDSD Application Completeness Express REVIEW COMPLETED
05/24/2023 Site Zoning REVIEW COMPLETED zoning stamp not required