Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2023 Site Zoning APPROVED
02/28/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/14/2023 Residential Building REQUIRES RESUBMIT T22CM00487 R2
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. All construction drawings submitted after June 1, 2010. for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. The ordinance revision now requires a gray drain line discharge from one fixture for a one story dwelling. Additional gray fixture drains are optional. Show a bathing fixture drain looped 3’ beyond an exterior wall below grade before connection to the building drain. See details at https://www.tucsonaz.gov/pdsd/water-energy-conservation Add the appropriate gray water loop detail for the tub/shower on the ground floor without a stub out at sheet P012 and P022. Update detail P025 on P032: replace the two story detail with the ground floor loop detail.

SITE PLAN:

1. Show the location and size of a sewer line from the building to an HCS; requires coordination with Pima County Wastewater Management.

SECTIONS - DETAILS:

1. Attic space requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2.

ELECTRICAL PLANS:

1. Remove misleading notation item “C” at Electrical General Notes on E000. Three phase service is not available and “re-use” is not appropriate for new construction.
2. Update circuit #6 as kitchen and bathroom receptacles require separate (dedicated) circuits, E3703.2, E3901.3 and E3901.6.

Please contact the plans reviewer if you have any questions: