Permit Number: T22BU00386
Parcel: 13213066A

Address:
2805 S PARK AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - T22BU00386
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/16/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 There was no response letter submitted with this submittal.

2 Previous review comment #3 not addressed, ”3 Verify compliance with the 2012 City of Tucson Outdoor Lighting Code for the pool Lighting. See OLC Chapter 4 and 401.2.1(2). Show compliance on the pool plan, or provide evidence on the pool plan that this was satisfied on the building site lighting plan by others.”.
The total exterior unshielded lumen output for the entire parcel of this project including the Pool and spa lighting cannot exceed the lumen caps shown per table 401.1.

Ref; 2018 IBC section 107.2.1, 2017 NEC 2012 City of Tucson Outdoor Lighting Code.
04/27/2023 PDSD Application Completeness REVIEW COMPLETED