Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - T22BU00386
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/21/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/21/2023 | Commercial Electrical | REQUIRES RESUBMIT | Previous plan review comment not completely addressed; ‘Provide complete electrical plans’... 1 Show all pool electrical equipment locations, pumps, heaters, devices, and receptacles, etc. Correlate equipment power requirements and circuit designations with the Pool Power panel and panel schedule. 2 Provide a wiring diagram and show the locations for the disconnecting switches/divices for the pool and spa as required per NEC art 680.13 and 680.41. 3 Verify compliance with the 2012 City of Tucson Outdoor Lighting Code for the pool Lighting. See OLC Chapter 4 and 401.2.1(2). Show compliance on the pool plan, or provide evidence on the pool plan that this was satisfied on the building site lighting plan by others. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
||
02/07/2023 | PDSD Application Completeness | REVIEW COMPLETED |