Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22BU00386
Parcel: 13213066A

Address:
2805 S PARK AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - T22BU00386
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/21/2023 Commercial Electrical REQUIRES RESUBMIT Previous plan review comment not completely addressed; ‘Provide complete electrical plans’...

1 Show all pool electrical equipment locations, pumps, heaters, devices, and receptacles, etc. Correlate equipment power requirements and circuit designations with the Pool Power panel and panel schedule.

2 Provide a wiring diagram and show the locations for the disconnecting switches/divices for the pool and spa as required per NEC art 680.13 and 680.41.

3 Verify compliance with the 2012 City of Tucson Outdoor Lighting Code for the pool Lighting. See OLC Chapter 4 and 401.2.1(2). Show compliance on the pool plan, or provide evidence on the pool plan that this was satisfied on the building site lighting plan by others.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
02/07/2023 PDSD Application Completeness REVIEW COMPLETED