Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESTAMP - COMMERCIAL v.1
Permit Number - T22BU00014
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/14/2023 | Commercial Building | APPROVED | |||
04/19/2023 | Commercial Mechanical | APPROVED | |||
04/19/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
04/19/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Specify the materials used for the gas piping. Reference: Section 403.1, IFGC 2018. 2. State how the size of the natural gas piping was determined. Reference: Section 402.3, IFGC 2018. 3. Provide a tracer wire for any underground non-metallic gas piping. Reference: Section 404.17.3, IFGC 2018. 4. Show that the design for the openings of the sleeved gas pipe vent are capable of preventing the entrance of water or insects. Reference: Section 404.14.1, IFGC 2018. 5. Provide an accessible shut off valve for each appliance. Reference: Section 409.5, IFGC 2018. |
||
04/18/2023 | Fire New Construction | REVIEW COMPLETED |