Permit Number: T22BU00014
Parcel: 111086740

Review Status: Requires Resubmit

Review Details: RESTAMP - COMMERCIAL v.1

Permit Number - T22BU00014
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2023 Commercial Building APPROVED
04/19/2023 Commercial Mechanical APPROVED
04/19/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
04/19/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Specify the materials used for the gas piping. Reference: Section 403.1, IFGC 2018.
2. State how the size of the natural gas piping was determined. Reference: Section 402.3, IFGC 2018.
3. Provide a tracer wire for any underground non-metallic gas piping. Reference: Section 404.17.3, IFGC 2018.
4. Show that the design for the openings of the sleeved gas pipe vent are capable of preventing the entrance of water or insects. Reference: Section 404.14.1, IFGC 2018.
5. Provide an accessible shut off valve for each appliance. Reference: Section 409.5, IFGC 2018.
04/18/2023 Fire New Construction REVIEW COMPLETED