Permit Number: T21CM09659
Parcel: 133367940

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T21CM09659
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/28/2022 Fire New Construction APPROVED
12/28/2022 NPPO APPROVED
01/25/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/25/2023 Residential Building REQUIRES RESUBMIT T21CM09659
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

Clarify if the Guest House structure is a sleeping quarters (without kitchen) or an Accessory Dwelling Unit (ADU) which has a maximum size of 1000 SF and requires collection of impact fee. Verify all requirements with the Zoning Section.

Each dwelling unit with kitchen requires a separate Pima County assigned street address, R319. Notate each dwelling address on the site plan (or remove cooking appliances).

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Identify the utility lines requiring upgrade or replacement.
2. Show a street address for each dwelling on the site plan, R319.

PLANS:

1. Notate a cool (white) roof finish as required by the ADU provisions.
2. Provide manufacturer’s calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or notate the requirement for deferred submittal, R106.1.

SECTIONS - DETAILS:

1. Show the total attic vent opening size using 1 to 150 of attic area with insulation at the ceiling in compliance with R806.2.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for water meter size in compliance with P2903.7. Show an appropriate size for supporting the existing and proposed dwellings.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A two or three bedroom dwelling under 1501 SF requires a 45 CFM continuous setting.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical plans if system calculations will be provided by deferred submittal.

ELECTRICAL PLANS:

1. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Show an underground feeder from a metered service panel to the more distant dwelling.
2. Update the Riser Diagram for the close dwelling and the feeder size to the detached dwelling panel per TEP coordination, NEC 225.30 and E3403.

OUTDOOR LIGHTING CODE

1. Update the Outdoor Lighting Calculation; show the unshielded limit for area E3 with 11,000 lumens per acre. This was changed with the latest code addition.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
01/11/2023 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM09659
310 N Schrader Ln – RX-1
(1st Review)

TRANSMITTAL January 11, 2023

This site is located in the RX-1 zone (UDC 4.7.6). A single-family residence is a permitted use in this zone (Table 4.8-1) subject to Use Specific Standards 4.9.7.B.6, .8, & .9.

1. As you are proposing a 2nd dwelling unit and per UDC TABLE 6.3-1.A: DIMENSIONAL STANDARDS FOR THE RH, SR, SH, RX-1, & RX-2 ZONES, RX-1 Zone, only one dwelling unit is allowed on this site unless you develop this as an Accessory Dwelling Unit (ADU) and is subject to UDC Articles 4.9.7.B.6, 8, & 9 and 6.6.3. It appears that the proposed guest house exceeds the allowed square footage, see Article 6.6.3.B.5.

2. There appears that a second electrical meter is planned. As this site does not allow 2 dwelling units a second meter is not allowed.

3. Based on current aerial photos there are several detached accessory structures located on this site. Show all structures on the plot plan along with perimeter yard setback dimensions. Zoning was able to find any record of permits or compliance reviews for these structures. Either provide copies of the permit documents with the next submittal or include in this permit. If the structures do not meet perimeter yard setback a neighbor’s setback waiver is required. Per UDC Article 6.6.2.D An accessory structure that exceeds the allowable height of a wall within a perimeter yard and is detached from a principal structure shall comply with the perimeter yard width standards of the principal structure, except that the accessory structure may be built to a parcel line with the consent of the adjoining or, when separated by an alley, adjacent property owner(s). To secure this neighbor setback waiver the following statement must be provided on the plot plan and be signed and dated by the adjacent property owner(s):
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
12/28/2022 PDSD Application Completeness Express REVIEW COMPLETED