Permit Number: T21CM08393
Parcel: 13733909C

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - T21CM08393
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2023 Water Sterilization Report (Deferred Submittal) APPROVED
03/14/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/14/2023 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT 1. The balance report shows that RTU-2, which serves the kitchen and BOH, is not within 10% of design air flow. Although the unit is drawing in sufficient outside air, many of the air outlets do not supply sufficient air flow to much of the area served. Increase the air flow rate for RTU-2 to within 10% of the design air flow rate and rebalance the system. Reference: Section 403.3.1.3, IMC 2018.
2. The balancing technician noted air leakage of the grease duct for KH-1 at the fan connection. Seal the fan connections per Section 506.3.2.3, IMC 2018.
03/14/2023 Special Inspection Certificate Review (Deferred Submittal) REVIEW COMPLETED