Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T21CM07846
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/27/2022 | Site Zoning | APPROVED | |||
11/18/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/18/2022 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: T21CM07846 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Conditionally Approved NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances. BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Denied First Revised plan Plumbing review: 1). Plan page P202 clouded note#15 states 3/4" gas up from below, that doesn't correlate with preceding & continuing pages all show 2" gas? plan pages need to correlate. -IFGC 106.3.1, 402.4 2). Plan page M202 3rd floor mech room detail #2 shows pipe work for WH3, WH4, WH7, that doesn't correlate with plan page P204 which only shows WH3, WH4, & a stub for a future water heater? plan pages need to correlate -IFGC , IPC 106.3.1 If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
11/10/2022 | Fire New Construction | REQUIRES RESUBMIT | Add mechanical plans showing modifications of the pneumatic dampers to how they are being controlled and the connection to the existing for the rest of the building for smoke control system. Questions: Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |