Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - T21CM07725
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2023 | Site Zoning | APPROVED | |||
| 04/10/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/10/2023 | Residential Building | REQUIRES RESUBMIT | Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Update the gas line table showing the BTU demand and length of line to each gas appliance from the meter for determining the correct pipe diameter. A 140,000 Btu appliance requires a 3/4" branch line if more than 10 foot developed length is used. The main line for three appliances within the building may require a 1" size. | ||
| 03/16/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |