Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/17/2023 | External Reviewers - SAFEBuilt | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Conditionally Approved Reason: Date Completed : 7/16/2023 10:04:15 AM Electrical Review of Riser By: Ron Ross PE Approved with the following conditions. Reviewer’s Response: Design shows enclosed Circuit Breakers instead of 400 amp disconnects. Disconnect/Circuit Breaker size has to comply with Table 220.84. Perform calculation. If the required size is over 400 amps, Resubmit with upsized conductors, the required OCP, and calculations to show the correct size is provided. There is no metering shown for the individual units. Add metering or meter stacks if owner is metering units (can call out as “FUTURE” if not available at time of construction). Also, missing DP4, but show two DP3 panels. |
||
07/17/2023 | Bldg Permits - Post Review | REVIEW COMPLETED | |||
07/10/2023 | PDSD Application Completeness | REVIEW COMPLETED |