07/17/2023 External Reviewers - SAFEBuilt APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/16/2023 10:04:15 AM
Electrical Review of Riser
By: Ron Ross PE
Approved with the following conditions.
Reviewer’s Response: Design shows enclosed Circuit Breakers instead of 400 amp disconnects.
Disconnect/Circuit Breaker size has to comply with Table 220.84. Perform calculation.
If the required size is over 400 amps, Resubmit with upsized conductors, the required OCP, and calculations to show the correct size is provided.
There is no metering shown for the individual units. Add metering or meter stacks if owner is metering units (can call out as “FUTURE” if not available at time of construction).
Also, missing DP4, but show two DP3 panels.