Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - T21CM05814
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/19/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/19/2023 | Air Balancing/Commissioning Report (Deferred Submittal) | REQUIRES RESUBMIT | 1. The correct address of the new Animal Welfare Center is 1635 W Roger Road. 2. The page showing the test results for HP 5 is cut off. 3. The supply air flow from HP 6 to Isolation Room 1 is 17% below the design air flow rate. |
||
12/19/2023 | PDSD Application Completeness | REVIEW COMPLETED |