Permit Number: T21CM05716
Parcel: 115052420

Address:
244 W FLORES ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T21CM05716
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/13/2023 Commercial Mechanical REQUIRES RESUBMIT Comment not addressed. [second comment: Specify the exhaust flowrate for the kitchen hoods. [Initial comment: Ventilation for kitchens in private dwellings requires a minimum of 25 CFM exhaust per room with no recirculation of air (e.g. specify the exhaust flowrate for the kitchen hood). Reference: Table 403.3.2.3, IMC 2018.]
02/10/2023 PDSD Application Completeness REVIEW COMPLETED