Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T21CM05716
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/13/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/13/2023 | Commercial Mechanical | REQUIRES RESUBMIT | Comment not addressed. [second comment: Specify the exhaust flowrate for the kitchen hoods. [Initial comment: Ventilation for kitchens in private dwellings requires a minimum of 25 CFM exhaust per room with no recirculation of air (e.g. specify the exhaust flowrate for the kitchen hood). Reference: Table 403.3.2.3, IMC 2018.] | ||
02/10/2023 | PDSD Application Completeness | REVIEW COMPLETED |