Permit Number: T21CM05525
Parcel: 11451206B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - T21CM05525
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2024 Site Engineering NOT REQUIRED Shared Studio Session. Master Permit T21CM05449 with reviews to be reflected on T21CM05523, T21CM05524, T21CM05525, T21CM05526, T21CM05527, T21CM05528, T21CM05529, T21CM05530, T21CM05531, T21CM05532, T21CM05533, T21CM05534, T21CM05535, T21CM05536, T21CM05537, T21CM05538, T21CM05539
10/11/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT Shared Studio Session. Master Permit T21CM05449 with reviews to be reflected on T21CM05523, T21CM05524, T21CM05525, T21CM05526, T21CM05527, T21CM05528, T21CM05529, T21CM05530, T21CM05531, T21CM05532, T21CM05533, T21CM05534, T21CM05535, T21CM05536, T21CM05537, T21CM05538, T21CM05539
10/04/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Shared Studio Session. Master Permit T21CM05449 with reviews to be reflected on T21CM05523, T21CM05524, T21CM05525, T21CM05526, T21CM05527, T21CM05528, T21CM05529, T21CM05530, T21CM05531, T21CM05532, T21CM05533, T21CM05534, T21CM05535, T21CM05536, T21CM05537, T21CM05538, T21CM05539

Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Approved with Comments
Reason:
Date Completed : 8/7/2023 6:10:48 PM






Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 8/2/2023 10:25:20 AM





Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Approved with Comments
Reason:
Date Completed : 7/28/2023 7:23:26 PM





Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 7/27/2023 4:58:49 PM




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 10/3/2024 9:09:10 PM
Second Revised Plan Plumbing Review: comments 2 & 3 remain
Resolved-1). Clouded Site utility piping plans & landscaping plan pages Sheet 1 thru L-12 not provided as shown on plan page T1 -IPC 106.3.1 (needs to correlate with the revised plumbing pages) Un-resolved-2). FS1 on plan page P1.9 can't be located at exterior . -IPC 1101.3 ( suggest relocate FS1 to interior or delete & pipe condensate to mop sink) **Duct work not an approved cover for floor sink & can still receive ground water**
Un-resolved-3). Plan page P1.7: The required bottlless water dispenser P6c is not shown on plumbing piping plan page P1.7, but is shown on plan page P4.2 fixture schedule which shows a drain & water connection. -IPC 106.3.1, Tucson IPC amendment 410.4 **still missing drain & vent illustrations as stated on P4.2**
Resolved-4). The P1 toilets on sanitary riser detail; #1 on plan pages P2.2, P2.3 are not vented properly -IPC 901.2.1
Resolved-5). The P1 toilets on sanitary riser detail; #1, #2, #4 , #5 & #6 on plan page P2.1 are not vented properly -IPC
901.2.1
09/27/2024 PDSD Application Completeness Express REVIEW COMPLETED