Permit Number: T21CM05524
Parcel: 11451206B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T21CM05524
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2023 Site Zoning APPROVED
08/21/2023 Water - PDSD APPROVED Shared Studio Session 783-877-878 Master Permit T21CM05449, T21CM05523, T21CM05524, T21CM05525, T21CM05526, T21CM05527, T21CM05528, T21CM05529, T21CM05530, T21CM05531, T21CM05532, T21CM05533, T21CM05534, T21CM05535, T21CM05536, T21CM05537, T21CM05538, T21CM05539, TC-COM-1122-00133, TC-COM-1222-00257, TC-COM-1222-00258, TC-COM-1222-00259
08/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/08/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/7/2023 6:10:48 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 8/2/2023 10:25:20 AM



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/28/2023 7:23:26 PM
Approved/subject to field approval



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 7/27/2023 4:58:49 PM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 8/1/2023 6:18:12 AM
First Revised Plan Plumbing Review:
1). Clouded Site utility piping plans & landscaping plan pages Sheet 1 thru L-12 not provided as shown on plan page T1 -IPC 106.3.1 (needs to correlate with the revised plumbing pages)

2). FS1 on plan page P1.9 can't be located at exterior . -IPC 1101.3 ( suggest relocate FS1 to interior or delete & pipe condensate to mop sink)

3). The required bottlless water dispenser P6c is not shown on plumbing piping plan page P1.7, but is shown on plan page P4.2 fixture schedule which shows a drain & water connection. -IPC 106.3.1, Tucson IPC amendment 410.4

4). The P1 toilets on sanitary riser detail; #1 on plan pages P2.2, P2.3 are not vented properly -IPC 901.2.1

5). The P1 toilets on sanitary riser detail; #1, #2, #4 , #5 & #6 on plan page P2.1 are not vented properly -IPC 901.2.1
07/27/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
07/26/2023 Fire New Construction REVIEW COMPLETED
07/25/2023 PDSD Application Completeness Express REVIEW COMPLETED Shared Studio Session 783-877-878 Master Permit T21CM05449, T21CM05523, T21CM05524, T21CM05525, T21CM05526, T21CM05527, T21CM05528, T21CM05529, T21CM05530, T21CM05531, T21CM05532, T21CM05533, T21CM05534, T21CM05535, T21CM05536, T21CM05537, T21CM05538, T21CM05539, TC-COM-1122-00133, TC-COM-1222-00257, TC-COM-1222-00258, TC-COM-1222-00259