Permit Number: T21CM04377
Parcel: 132131370

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - T21CM04377
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2023 Bldg Permits - Post Review PENDING ASSIGNMENT Utilize Studio Session 540-565-641 for Review
03/13/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T21CM4334/4376-4378 New Apartment Buildings

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Structural Calculations for Foundations/Retaining Walls and Columns for the proposed canopy per Section 1601.1 of International Building Code 2018.
2. Provide Wind Load Calculations for the proposed canopy per Section 1609 of International Building Code 2018.
3. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
First revised Plan Plumbing review:
1). plan page P4.05 #9 upstack needs to tie in downstream of the bath group -IPC 912.1
2). plan page P4.05 needs to illustrate the water piping to the studio unit. -IPC 106.3.1
3). plan page P4.05 needs to illustrate the vent piping -IPC 106.3.1, 901.2.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/16/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T21CM04377
1102 E 36TH ST Zoning PAD-15

TRANSMITTAL DATE:‎March 16, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Zoning is unable to review this submittal, Please submit a plan set, The revision letter was the only thing submitted.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
02/21/2023 PDSD Application Completeness REVIEW COMPLETED