Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - T21CM03324
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/30/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/30/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. The line diagram shows panel ‘R’ as new, and the Keyed Note #12 states Existing. The site plan also shows Existing. Please clarify. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
08/30/2023 | PDSD Application Completeness | REVIEW COMPLETED |