Permit Number: T21CM03323
Parcel: 12217297D

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T21CM03323
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/14/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. The electrical line diagram shows the existing electrical service fed underground by the Utility. The new upgraded service must also be fed underground per the 2018 IBC City of Tucson adopted Amendments section 112.1.1. An underground service Waiver can be applied for if desired. The Waiver form can be downloaded from the PDSD website and submitted for review by the inspections department.

2. Indicate conduit, conductor sizes and types for the service entrance conductors in the riser conduit.

Ref; 2018 IBC section 017.2.1, 112.1.1, 2017 NEC.
09/13/2023 PDSD Application Completeness Express REVIEW COMPLETED