Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - T21CM03323
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/28/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/28/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The requested Service waiver was denied to allow an overhead fed electrical service. The original service is fed underground. A revised electrical plan was submitted on 4-1-2024 showing a electrical design change to feed the Service utilizing an underground service lateral, however there were electrical comments concerning downstream feeders to panels. Now the plans are resubmitted with the Service drop back to overhead, which was denied originally... Please clarify. Ref; 2018 IBC section 107.2.1 and 2018 IBC City of Tucson adopted Amendments section 112.1.1, 2017 NEC |
||
| 05/13/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |