Permit Number: T21CM03323
Parcel: 12217297D

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.6

Permit Number - T21CM03323
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.6
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/16/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Ref; Plan Sheet E2u. The new feeder for existing panel ‘B’ is undersized (4#1 conductors) per Keynote #9. Please revise to the correct sizes AWG per NEC art 240, and 310.15(B)(16).

2 The electrical Line Diagram shows panel ’R’ as New and the Keynote #12 shows it as existing. Please clarify.

3 Show the location and circuit designation for the existing Condensing Unit fed by the New Panel ‘R1’. NEC art 408.4.

Ref; 2018 IBC section 107.2.1, 2017 NEC
04/03/2024 PDSD Application Completeness Express REVIEW COMPLETED