Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.6
Permit Number - T21CM03323
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.6
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/16/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Ref; Plan Sheet E2u. The new feeder for existing panel ‘B’ is undersized (4#1 conductors) per Keynote #9. Please revise to the correct sizes AWG per NEC art 240, and 310.15(B)(16). 2 The electrical Line Diagram shows panel ’R’ as New and the Keynote #12 shows it as existing. Please clarify. 3 Show the location and circuit designation for the existing Condensing Unit fed by the New Panel ‘R1’. NEC art 408.4. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
| 04/03/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |