03/21/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/21/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Attempted to call the EE of records office by phone to discuss at 9am today, no answer and no message system available. 1 Ref; Line Diagram. Keyed Note #7 is used for the feeder information for existing panel ‘R’ is not correct. Please clarify and resubmit revised plan. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
03/20/2023 | PDSD Application Completeness | REVIEW COMPLETED |