Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - T21CM02643
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/23/2023 | Commercial Electrical | REQUIRES RESUBMIT | The previous electrical review comment not addressed; Verify that the existing Meter/CT enclosure is listed or suitable for the use as a feeder or conductor junction enclosure and meets the requirements of NEC art 110.3, 314.28, 314.0. The ‘PLAN REVISION LETTER’ made reference to ‘DELTA 3’. There are no DELTA 3’s in the submitted electrical plans. Please clarify. |