Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - T21CM02450
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/12/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/12/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical review comments and provide a written response. New electrical service secondary feeders must be installed underground, unless the existing feeders were already installed overhead. Per 2018 IBC Amendments. However, an underground service waiver can be submitted for approval by the Building Official. The form can be downloaded from the PDSD website. www.tucsonaz.gov/pdsd. ADD new Section 112.1.1 as follows: Section 112.1.1 Service conductors. All service conductors, power and communication, shall be installed underground for all new construction. The requirement for underground conductors may be waived by the Building Official where: 1. Existing buildings on the block are served with overhead conductors or where a lot to be constructed upon is one of three or fewer abutting vacant lots making up less than 40 percent of the total acreage of the block (not including street or right-of-way) or where a vacant area is less than 60,000 square feet. 2. The installation, when compared to the use of overhead conductors, would create a hazard or not be feasible. A feasibility study will be required at the time the request for waiver is made. Ref;2018 IBC City of Tucson Amendments. |
||
| 03/21/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |