Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - T21CM01487
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/02/2023 Commercial Mechanical REQUIRES RESUBMIT Comment not addressed. The Valencia Kool Box report shows the insulating value of the foam insulation but the comment relates to the electrical energy input of the refrigeration equipment (Watt-hour) versus the cooling capacity (BTU) of the system. [Second comment: Comment not resolved. See Table C403.10.2.1(3) for the minimum required annual walk-in energy factor (BTU/Watt-hour) for an outdoor, medium temperature system.] [Initial comment: Show that the walk-in cooler/freezer meets the efficiency requirements of Section C403.10.2.1, IECC 2018.]
01/06/2023 PDSD Application Completeness Express REVIEW COMPLETED