Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - T21CM01487
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/02/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/02/2023 | Commercial Mechanical | REQUIRES RESUBMIT | Comment not addressed. The Valencia Kool Box report shows the insulating value of the foam insulation but the comment relates to the electrical energy input of the refrigeration equipment (Watt-hour) versus the cooling capacity (BTU) of the system. [Second comment: Comment not resolved. See Table C403.10.2.1(3) for the minimum required annual walk-in energy factor (BTU/Watt-hour) for an outdoor, medium temperature system.] [Initial comment: Show that the walk-in cooler/freezer meets the efficiency requirements of Section C403.10.2.1, IECC 2018.] | ||
| 01/06/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |