Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - T21CM00864
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/14/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/14/2023 | Air Balancing/Commissioning Report (Deferred Submittal) | REQUIRES RESUBMIT | Fan Coils FC-12, FC-15, and FC-18 have insufficient outside air compared to the design flow rates (49%, 40%, and 46% respectively). Have the engineer review the air balance report and determine what corrective actions need to be taken and then resubmit the balance report. | ||
03/13/2023 | Water Sterilization Report (Deferred Submittal) | REQUIRES RESUBMIT | The water disinfection report was not included in this submittal |