Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/06/2023 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT 1. The test & balance report does not include the hood performance test results. Reference: Section507.6, IMC 2018.
2. The total air flow for unit AC-N5 is 27% below the specified air flow rate. The engineer of record shall review the situation and determine the course of action prior to the air balance report being resubmitted. Reference: Section 403.3.1.5, IMC 2018.