Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - T21CM00759
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/06/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/06/2023 | Air Balancing/Commissioning Report (Deferred Submittal) | REQUIRES RESUBMIT | 1. The test & balance report does not include the hood performance test results. Reference: Section507.6, IMC 2018. 2. The total air flow for unit AC-N5 is 27% below the specified air flow rate. The engineer of record shall review the situation and determine the course of action prior to the air balance report being resubmitted. Reference: Section 403.3.1.5, IMC 2018. |
||