Permit Number: T21CM00759
Parcel: 11918040C

Address:
3410 S 16TH AV

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - T21CM00759
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/21/2024 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT Section 507.6, IMC 2018 calls for the hood testing to verify “proper operation as specified in this chapter...” Section 507.6.1, IMC 2018 describes the capture and containment testing that is used to verify that the hood operates correctly. Provide a statement for each hood that verifies that the hood was able to capture and contain smoke from the hood during actual or simulated operation. [Initial comment: The test & balance report does not include the hood performance test results. Reference: Section507.6, IMC 2018.]