Permit Number: T20CM09121
Parcel: 123080560

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T20CM09121
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2023 Commercial Plumbing APPROVED
12/05/2023 Commercial Structural APPROVED
12/01/2023 Site Zoning APPROVED
12/12/2023 Site Engineering NOT REQUIRED
12/12/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
12/11/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. There are already 2 electrical services attached in different locations on the same building. Adding a 3rd service will only be allowed by Special Permission in compliance with NEC art 230.2(A), (B), (C), (D), and (E). Please justify installing a 3rd electrical service in lieu of upgrading an existing service.

2. Multiple services attached on the same building are required to have a common grounding electrode system per NEC art 250.58.

3. Verify GFI protection is provided for receptacles located within 3’ of the sinks in the LAB area.

Ref; 2018 IBC section 107.2.1, 2017 NEC.
12/05/2023 Commercial Mechanical REQUIRES RESUBMIT Relocate the termination of the existing exhaust fan (Keynote 2) to a point 10-feet from the existing evaporative cooler (Keynote 3). Reference: Section 501.3.1 (3), IMC 2018.
12/11/2023 Fire New Construction REVIEW COMPLETED
11/30/2023 PDSD Application Completeness REVIEW COMPLETED